Up to three channels in a single instrument
The R&S®HMP DC Power supplies are primarily designed for industrial use. With two or three output channels and up to 10 A output current, these rugged instruments are ideal for a wide variety of applications. They offer high efficiency with low residual ripple and many protection functions.
모델
모델명 |
출력 채널 수 |
최대 출력 파워 |
채널 당 출력 전압 |
채널 당 출력 전류 |
R&S®HMP2020 |
2 |
188 W |
0 V to 32 V |
channel 1: 10 A, channel 2: 5 A |
R&S®HMP2030 |
3 |
188 W |
0 V to 32 V |
5 A |
주요특징
- 2 or 3 channels with max. 188 W total output power
- Maximum output voltage of 32V per channel
- Maximum output power per channel: 80 W; except R&S®HMP2020 (CH1: 160W)
- Maximum output current per channel: 5 A; except R&S®HMP2020 (CH1: 10 A)
- Electronic fuse (OCP), adjustable maximum voltage (OVP), overtemperature protection (OTP)
More than meets your daily needs
- All channels galvanically isolated and floating
- All channels have the same voltage range
- All channels have overload and short-circuit protection
- Parallel and serial operation
- Constant voltage and constant current modes
- Tracking and link functions
- Protection functions to safeguard instrument and DUT
- Modern instrument concept: small, compact and quiet
Easy operation
- Intuitive to use
- Color coding of operating states
- EasyArb function for all channels
- Save and recall instrument settings
Ideal for labs and test systems
- Tailored for use in labs and system racks
- Sense function for more stringent accuracy requirements
- Connections on front and rear panels
- Remote control of instrument functions
주요 스펙
Electrical specifications
|
Number of output channels |
|
2/3 |
Total output power |
|
max. 188 W |
Maximum output power per channel |
|
80 W; except R&S®HMP2020, CH1: 160 W |
Output voltage per channel |
|
0 V to 32 V |
Maximum output current per channel |
|
5 A; except R&S®HMP2020, CH1: 10 A |
Voltage ripple and noise (20 Hz to 20 MHz) |
|
< 1.5 mV (RMS) (meas.) |
Current ripple and noise (20 Hz to 20 MHz) |
|
< 1 mA (RMS) (meas.) |
Load recovery time*1) |
|
< 1 ms (meas.) |
Programming/readback resolution |
Voltage |
1 mV |
|
Current |
< 1 A: 0.1 mA (10 A CH: 0.2 mA); ≥ 1 A: 1 mA |
Readback accuracy (± (% of output + offset)) |
Voltage |
< 0.05% + 5 mV |
|
Current |
< 0.1% + 2 mA |
Special functions
|
Measurement functions |
|
voltage, current |
Protection functions |
|
OVP, OCP, OTP |
FuseLink function |
|
● |
Fuse delay at power-up |
|
● |
Sense function |
|
● |
Sink mode |
|
– |
Output sequencing |
|
– |
Trigger input/output |
|
– |
Arbitrary function |
|
● (EasyArb) |
Analog/modulation interface |
|
– |
Data logging |
|
– |
Display and interfaces
|
Display |
|
240 × 64 pixel LCD |
Rear panel connections |
|
connector block with 4 lines per channel |
Remote control interfaces |
|
standard: USB, LAN; optional: IEEE-488 (GPIB), RS-232 |
General data
|
Dimensions (W × H × D) |
|
285 × 93 × 405 mm |
Weight |
|
7.8 kg/8.0 kg |
Rack installation |
|
R&S®HZ42 option |